FR200 with prismatic PMMA enclosure
Version with single battery emergency light element | insulation class I
FR200 damp-proof diffuser luminaire for ceiling surface mounting, suspended mounting or mounting to a rail | direct extremely wide distribution with ceiling illumination**; with prismatic cover | with ECG or LLCG, additionally with single battery emergency light element | housing of glass-fibre reinforced polyester, grey; cover of PMMA
Protection rating: IP65 Insulation class: I Protection symbol: F ** direct distribution via supplementary reflector Electrical
Luminaire for operation on 'normal mains' or via the integral self-contained supply | wired ready for connection, with 4-pole connection terminal (3-pole for normal mains with switched phase* + single pole for additional unswitched phase* for emergency light element), max. 2.5mm² | cable entry suitable for cables or conduits with Ø= 8.5..13.5mm, with twin entry grommet (accessory) for 2 cables Ø= 8.4..12mm | with ECG, with single battery emergency light element* (for 1h operation) and with LED (for optical self-test functioning control of battery***) | luminaire suitable for through-wiring (with special wiring sets) within luminaires
Rated voltage= 220..240V / AC 50..60Hz
* the switched phase (terminal >L1<) and the unswitched phase (terminal >L2<) must have the same phase angle | the emergency battery is charged over the unswitched phase and the luminaire is informed of the operational condition (normal or emergency): - non-switched phase in operation: ---> normal operation (luminaire operation via mains, normal on/off switching)
- non-switched phase missing: ---> emergency operation (via battery) | luminaire is switched on even when luminaire was switched off in normal operation
*** LED signals: Green LED: battery connected and charged Green blinking LED: battery being charged Red blinking LED: battery not connected or defect Yellow blinking LED: automatic discharging / charging of battery
Emergency operation with reduced lumen output: Lumen output phi=12% (T26 lamping, 58W) With twin-lamp luminaires: operation with one lamp
permissible ambient temperature for luminaire with single battery emergency light element: 0°C to 25°C
|